Stripping Dimension
Concerning the necessary cable jacket length which has to be removed, refer to the product summary, section "stripping length".
Select according to the type number.
Mounting steps
1. Remove Cable Jacket
Cut out the necessary cable jacket length according to the "stripping length" dimension. For this operation, take care to select a straight section of the cable.
Important: start cutting in a trough of the corrugation with corrugated cables. Do not damage the copper tube respectively the cable screen.
2. Prepare Grounding Kit
Open the grounding kit.
3. Fix Grounding Kit to Cable
Push the contact bracket "C" over the cable copper tube or screen. Apply grease to the outer surface of the rubber sealing. Close the outer bracket of the kit and tighten the screw.
4. Fix Grounding Kit to Grounding System
Connect the grounding kit to the lightning protection system (e.g. metal mast, down conductor, bonding system). Fix the cable of the kit with its M8 screw to the grounding/bonding facility.
5. Recommended: Wrap the Cable grounding section
Apply an additional sealing by wrapping the cable clamping section with self-vulcanizing tape.